Duplex
Horizon
Advantages of Compact District Heating Substation
- Reduction of construction cost – No additional costs due to on-site piping works, on-site supervision and schedule conflicts with other processes.
- Reduction of unit cost – Standardized design, production and setting at factory.
- One point contact for maintenance and service for each component of the unit.
- Supplier’s guarantee for module and for each component.
- Short construction schedule – Once connected it’s ready to operate.
Duplex
- Top view
- Front view
Technical Spectification
Heating and hot water supply pipe diameter table for district heating by heat duty | |||||||||
Heating Heat Duty | Heating Primary Circuit | HWS, HWR | Hot Water Supply Heat Duty | HWS Heat Duty | Water Supply Line | Return Line | DHWR | DIMENSION | Remarks |
(Mcal/h) | (A) | (A) | (Mcal/h) | (A) | (A) | (A) | (A) | (AxB mm) | |
~170 | 40A | 65A | ~105 | 32A | 40A | 40A | 32A | 3500 x 3600 | Sole |
~205 | 40A | 80A | ~164 | 40A | 50A | 40A | 50A | 3000 x 3400 | Duplex with DX-3D heating |
~260 | 50A | 80A | ~307 | 50A | 65A | 40A | 65A | 3000 x 3400 | Duplex with DX-3D heating |
~384 | 50A | 100A | ~463 | 65A | 65A | 40A | 80A | 3000 x 3400 | Duplex with DX-22D heating |
~510 | 65A | 100A | ~649 | 65A | 80A | 40A | 80A | 3200 x 3600 | Duplex with DX-22D heating |
~680 | 65A | 125A | ~684 | 80A | 80A | 40A | 100A | 3200 x 3600 | Duplex with DX-22D heating |
~811 | 65A | 125A | ~684 | 80A | 80A | 40A | 100A | 3200 x 3600 | Duplex with DX-22D heating |
~893 | 80A | 125A | ~684 | 80A | 80A | 40A | 100A | 3200 x 3600 | Duplex with DX-22D heating |
~1244 | 80A | 150A | ~718 | 80A | 80A | 40A | 100A | 3500 x 3600 | Duplex with DX-22D heating |
~1471 | 100A | 150A | ~840 | 80A | 100A | 50A | 100A | 3500 x 3600 | Duplex with DX-22D heating |
~2940 | 100A | 200A | ~1150 | 100A | 100A | 50A | 125A | 3000 x 5000 | Horizon |